Hyjet FPC Series

Functions

  • Level control mode – Level empty operation controlled by up to 5 float switches: Low level, duty stop, duty start, standby start and high level.
  • Pressure control mode – Pressure boost operation controlled by up to 3 pressure switches: Duty start, standby start and low pressure.
  • Duty sharing and alternation – The duty pump alternates on pump start and after 30 minutes of continuous running in alternation mode, or 6 hours of accumulated running in recirculation mode.
  • Staggered pump start – Prevents excessive current draw and reduces water surge.
  • Manual pump control – Manual pump mode with optional 5-minute timeout to revert to auto mode.
  • System enable input – Enables and disables the system in auto mode.
  • Static duty mode – No duty alternation, for applications using a smaller duty pump that always starts first.
  • Smart chirp mode alarms – Audible alarm automatically silences after 5 minutes if not muted, then chirps every 5 minutes.

Current Sensing Ratings

Fault Protection

  • High-level alarm – Alarms after a 15-minute delay with auto reset in stormwater mode, or after 1 minute with manual reset only in sewage mode.
  • Low-level protection – Alarms and shuts down pumps on a low level, manual reset only.
  • Low-pressure protection – Alarms and shut down pumps if low-pressure input is closed for 60 seconds.
  • Prime loss protection – Alarms and shuts down running pumps if there is no flow for 30 seconds.
  • Pump anti-seize protection – Runs pumps periodically during low use to prevent seizing.
  • Pump current sensing – Provides adjustable pump overload, undercurrent and zero current protection.

Additional options are added to the end of the code after the overload rating, eg: FPC-82143-LR/BMS. Most options can only be added to the inner door version.

  • /BMS – With BMS module providing volt-free outputs for power on, low and high level, individual pump run and fault and common fault
  • /SMS – With ME-Link module for SMS alarm/status messaging
  • /RMC – With rain/mains changeover control module and 12Vdc pulse latching solenoid valve
  • /GEN – With generator input socket and manual changeover switch
  • /ATS – With automatic generator changeover switch
  • /RCBO – With individual pump RCBO protection
  • /CON – With a conductivity module and up to 5 probe inputs
  • /INT – With intrinsically safe input barrier relays
  • /TF – With tank fill control mode enabled
  • /MR – With max run protection enabled
  • /PL – With pump limit function enabled
  • /SRCAP – With start and run capacitors
  • /RCAP – With run capacitors
  • /BBHLS – With battery backup high-level alarm
  • /HWC – Configured for hot water circulation
  • /TC – With a time clock for time-of-day operation
  • /SS – With 316 stainless steel enclosure

Technical Data

Data sheet